Call Us Today:(+86) 153-0260-2812
ALL PRODUCTS
AIR FILTERS
Fan Filter Unit HEPA Filter Air Filters And Housing Carbon Filter Projector Air Filters
CLEAN ROOMS
Engineering Project Cleanroom Air Shower Air Shower Tunnel Clean Room Booth Air Shower Pass Box Laminar Flow Cabinet Sandwich Panels Cleanroom Doors &Window Stainless Steel Devices Air Diffusers Air Louvers
Customer Reviews
We have purchased 4 roller shutter doors for our candy factory,very fast delivery and good quality .customer is very satisfied.
—— Mr Anderson
We have been keeping a good contact for years, we visited them after the approval of our cleanroom construction apply, they quickly updated the detailed offer and drawing after talked. the completion is great and as proposed. We choose alpha clean again for our new plants cleanroom constructor.
—— Mr Mariefe
Very good HEPA filters for our pharmaceutical plant,we will purchase from you next time.
—— Mr mohammed
Newsletter

About the latest offers and deals Subscribe today!

SHARE TO:  

ClassI ISO5 Hospital operation room laminar flow ceiling
Product Details:

Dimension (W*D*H):2600mm*2400mm*450mm

In size (mm):

Type Suitable:operation room

Rated air flow:0.45m/s

Power:/

Material:power coated steel

Blowing side:downside laminar flow

Brand:alphaclean

Place of origin:shenzhen,china

Warranty:1 year

Detailed Product Description

In accordance with the purification class, laminar flow air supply ceiling is divided into Class 5/6/7/ 8 /9 (ISO14644-1) laminar flow air supply ceiling,or classified to burn ward, blood ward and ophthalmic operating room laminar flow air supply ceiling, etc.

laminar flow air supply ceiling materials and advantages

a. Plastic-sprayed electrolytic plate and stainless steel materials can be selected by customers.

b. The T type special aluminum configured with spring clip-on installation makes the maintenance and installation convenient and time-saving.

c: The DPP equalizer net makes the air more uniform and gentle. The medium speed airflow compensation device is optional.

d. The high efficiency air filter can be decorated to two kinds of air supply,side air supply and roof air supply. The non-standard dimension of laminar flow air supply ceiling can be made in case of special actual environment.

Ceiling Laminar air flow Parameters
Model P11-TH01-000 P11-TH02-000 P11-TH03-000 P11-TH03-001 P11-TH01-000 P11-TH04-000
Class Class 5 Class 6 Class 7/8/9 Burn ward Blood ward Ophthalmic OT
Ceiling dimension 2600*2400*450 2600*1800*500 2600*1400*500 2600*1400*500 2600*2400*500 1500*1500*500
Installation type and HEPA filter size laying
920*1140*69 920*840*69 920*610*69 920*610*69 920*1140*69 690*422*69
Hepa filter QTY 4 4 4 4 4 4
Air flow (m/s) 0.45 0.3 0.23 0.23 0.45 0.45
Initial pressure drop(pa) 125 100 80 80 125 125
Installation type and HEPA filter size Standing
610*305*292 610*305*292 610*305*292 610*305*292 610*305*292 610*305*292
Hepa filter QTY 8 up to 10 4 up to 6 2 up to 4 3 8 up to 10 4